19IOM-5WESTCAST, INC.260 NORTH ELM STREET WESTFIELD, MA 01085TEL. (413) 562-9631 FAX (413) 562-3799INSTALLERREAD THESE INSTRUCTIONS CAREFULLY. THEY
19A SERIES BOILERINSTALLATION INSTRUCTIONSFIGURE 11PAGE 10“A” - 1" TAP, PRESSURE CONTROLS“B” - 1 1/4" TAP, STEAM SAFETY VALVE“C” - 1" T
19A SERIES BOILERINSTALLATION INSTRUCTIONSvision problemsloss of muscle controlweaknessdizzinessheadachesnauseaWARNINGshortness of breathunclear think
WESTCAST, INC.260 NORTH ELM STREET WESTFIELD, MA 01085TEL. (413) 562-9631 FAX (413) 562-3799
PAGE 219A SERIES BOILERINSTALLATION INSTRUCTIONS— 3640 Burner Mounting Plate,Powerflame - 91/8" Opening13 60023 Burner Mounting Plate Rope, 1/4&q
3. CODES AND REGULATIONSAll work in connection with the boiler, burner and controlsmust be performed in strict accordance with requirements ofstate an
CAUTIONDue to the fact that the sections are top heavy, it isabsolutely necessary that the back section be supportedin such a manner as to prevent its
2. Water Boilers – The assembled boiler shall be subjectedto a hydrostatic test pressure not less than 1-1/2 times themaximum allowable working pressu
TABLE 5Feed water makeup requirements.NOTEThese recommendations are considered normal forcompact buildings on the basis of 80% receiver use.Where buil
FIGURE 6 — TANKLESS PIPINGFIGURE 7 — DUAL TANKLESS PIPING12. BURNER MOUNTING PLATE & TARGET WALLThe new target wall used on 3-6 section boilers mu
19A SERIES BOILERINSTALLATION INSTRUCTIONSPAGE 815. CONTROL LOCATIONSNOTEJacket front panel should be in place before controls onfront of front sectio
19A SERIES BOILERINSTALLATION INSTRUCTIONS19. OWNERS INSTRUCTIONSA. For best performance of the boiler, the followingsuggestions should be performed b